Part Number: ETI0001-1240
Rugged Mil Spec® Rack or Fixed Mount
1000 VA UPS and Frequency Converter
Used in Medical Applications
US Air Force ECMO Medical Patient Cart
Application
1.0 kVA Mil Spec UPS and Frequency Converter
Rugged Rack or Fixed Mount Unit
w/ Reduced Depth and Multiple Battery Modules for
Up to 4 Hours of Battery Backup between Locations
Accepts both Aircraft Power and Commercial Power

ETI0001-1240 Rugged Mil Spec UPS Standard Front Panel Layout,
Shown w/ Rack Flanges Mounted and One
Battery Expansion Module

ETI0001-1240 Rugged Mil Spec UPS Standard Rear Panel Layout,
Shown w/ One Battery Expansion
Module, w/o Rack Flanges When
Mounted in Lower Section of the Patient
Cart
The field proven Airborne Power® UPS line is ideally suited for military,
industrial, medical and telecommunications applications requiring high reliability, rugged
construction, compact size and light weight design. These units are equally
suited for use in shipboard, airborne, vehicular, field deployed or fixed
locations with controlled or uncontrolled environments. The
"ETI0001-1240" is being used by the US Air Force ECMO Cart project because
of their stringent performance and reliability requirements.
The heavy-duty chassis,
occupying only 3U (5.25" high) of rack space and 18.5" depth, has rounded metal corners
and rugged handles front and rear, aiding in safe handling. The companion 2U
(3.5" high) Battery Expansion Modules are designed to be daisy chained to bring the backup
time to 4 hours in the typical configuration. In the typical ECMO Cart
application, the base UPS unit and up to four Battery Modules are mounted in the
lower underside section of the patient cart. Both module chassis are
constructed of brushed aluminum to minimize overall weight. Internally, all major
components are well secured and electrically insulated to prevent damage due to shock and
vibration.
The internal shielded
input transformer provides galvanic isolation with provisions for domestic (115
VAC, CONUS) and optionally for international (230 VAC, OCONUS) input
voltages. Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. This special
transformer and filters result in ultra low input leakage current required for
medical applications. The unit also operates
as a frequency converter, taking 46-440 hertz input and converting it to clean,
uninterruptible 60 hertz power. The input switch and the galvanic isolation
transformer all provide a double pole isolated source for
systems or locations where phase references and grounding are not
consistent. For scenarios that need hospital grade power immediately and
no AC source is available to run the UPS, the Cold Start pushbutton allows the unit to
start and run from its
battery modules before external AC is available.
The LED arrays keep the
operator informed as to the unit's status including load and battery levels. The
high intensity audible alarm can be heard in high noise environments. All controls
and protective devices are brought to the front and rear panels with critical switches having finger
guards. Further, all front panel devices are recessed to prevent damage or accidental
operation. Various
optional power distribution controls are available which mount on the front panel or
remotely.
The rear panel provides a locking
connector for the input power and six hospital grade NEMA 5-15R output receptacles.
Multiple
input and output power panel options are available. Removable and washable air filters and a high capacity
stainless steel ball bearing fans provide
added protection in both controlled and hostile environments. The exhaust air is diverted out the front
vent, with alternate
air flow directions optional. The "ETI0001-1240" has the added benefit of having
both an internal battery and external battery expansion modules. The external
Battery Modules can be field replaced without having to shut the UPS down. This
allows the backup time to be extended even further. The optional Battery
Charger/Conditioner (which has aircraft and global input capability) is used
to maintain the spare Battery Modules in ready condition at all times. The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the
Battery
Technology section. The Status connector provides an
interface with optional computer software providing loss of AC and low battery status as well as
remote shut down capability.
See the Power Distribution Units section for a
listing of stand alone PDUs. See the N5 Series ETI0001-1479
for a version of this UPS with an integrated PDU and remote control.
Overall, the Airborne
Power line is uniquely qualified for critical
shipboard, vehicle, airborne or land based systems combining advanced modular design
features with highly reliable construction.
Technical Specifications:
P/N: ETI0001-1240
AC OUTPUT |
Output voltage: UPS |
120 VAC true sinewave standard, up to 600 VAC optional |
Output rating: UPS |
1000 VA standard in
4U x 18.5" deep
0.65-0.75 pf
standard, optional
configurations to 24,000 VA |
Non-linear load capacity: UPS |
Up to 100% non-linear load capability w/o
derating |
Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: UPS |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: UPS |
Less than 5.0% into 100% non-linear load |
Output frequency: UPS |
60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz
output available as an option |
Operational status |
Status, load and battery LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off
|
AC INPUT |
Input voltage selection: |
Nominal 115 VAC, optional
autoranging input of 85-270 VAC |
Input voltage tolerance: UPS |
85-135 VAC @ full
load without using battery, to 70 VAC @ 75% load |
Input frequency: |
From 46 Hz to 440 Hz
standard |
Input power factor: |
Better than 99% typically |
Input/output isolation: |
1000 VA, up to 120 dB common mode, <700
microampere leakage
Optional <50 microampere for commercial version w/o Mil Std 461 |
Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
Input control/protection: |
Guarded 2 pole switch w/ fuse, optional
circuit breaker
Cold start to turn on w/o AC present |
Input power connection: |
MS 3102A-22-2P, 3 pin,
threaded locking |
INTERNAL BATTERY |
Internal
battery
type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
Internal battery life: |
Rated for continuous service life of 5 years |
Internal DC protection: |
Front panel mounted fuse
standard |
Internal battery time: |
8+ minutes @ 100% load,
20+ minutes @ 50% (base UPS only) |
Internal battery recharge: |
Recharged to nominal in <8 hours |
Internal battery replacement: |
Drawout/plug-in module from front of unit |
EXTERNAL BATTERY |
External
battery
type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
External battery life: |
Rated for continuous service life of 5 years |
External DC protection: |
Rear panel mounted fuse
standard |
External battery time/module: |
65+ minutes @ 100% load,
130+ minutes @ 50% per module |
External battery recharge: |
Recharged to nominal in
twenty times the discharge time |
External battery replacement: |
Drawout/plug-in module from front of unit |
DISTRIBUTION PANEL |
Output circuits: |
Six outputs standard, optional configurations |
Output control: |
Optional remote control panel w/rocker
switches |
Output receptacles: |
NEMA 5-15R Hospital
Grade, 3 pin |
MECHANICAL |
Dimensions ( H x D x W ):
UPS
Each 2U Battery Module |
5.25 (3U) x 18.5 x 19.0 in
(133 x
470 x 483 mm)
3.50 (2U) x 18.5 x 19.0 in (89 x
470 x 483 mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices
patterns, others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable,
Horizontal/Vertical |
Unit weight:
UPS base unit only
Each 2U Battery Module |
74 lb. (34 kg) UPS
with lift handles front and rear
77 lb. (35 kg) Battery
with lift handles front and rear |
Audible noise: |
Less than 47 dB @ 5.0 ft., ANSI "A"
scale |
Cooling type: |
High capacity, positive pressure, forced air |
Cooling air direction: |
Rear intake, exhaust to front,
others optional |
Air intake filter: |
Washable metal filter media, others optional |
ENVIRONMENTAL |
Storage temperature: |
-40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
Operating temperature: |
-4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m) |
Operating elevation: |
Up to 15,000 ft (4,572 m), higher optional |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
|
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC Part 15, Class
A; EN55022; MIL
STD 461 |
OPTIONAL ACCESSORIES |
|
Autoranging International Input,
Cold Start, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source
Input, Battery Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power Distribution Units, Software
Interface, Asynchronous serial COM port, 10BaseT
Ethernet SNMP/HTTP port, Transport Cases,
Slides and Mounting Kits |