ETI0001-1287AA 1.0 kVA All of these products are manufactured by ETI in the United States.

Up
ETI0001-1202 1.5 kVA
ETI0001-1214 3.0 kVA
ETI0001-1229 2.0 kVA
ETI0001-1230 1.5 kVA
ETI0001-1230AA 1.5 kVA
ETI0001-1233 2.0 kVA
ETI0001-1233AA 2.0 kVA
ETI0001-1235 1.0 kVA
ETI0001-1237 2.0 kVA
ETI0001-1237AA 2.0 kVA
ETI0001-1240 1.0 kVA
ETI0001-1241 3.0 kVA
ETI0001-1242 1.0 kVA
ETI0001-1250 1.5 kVA
ETI0001-1251 1.5 kVA
ETI0001-1251AE 1.5 kVA
ETI0001-1252 1.5 kVA
ETI0001-1253 2.0 kVA
ETI0001-1254 2.0 kVA
ETI0001-1255 1.5 kVA
ETI0001-1285AA 1.5 kVA
ETI0001-1287AA 1.0 kVA
ETI0001-2205A3 5.0 kVA
ETI0001-2205E1 3.0 kVA
ETI0001-2205E2 3.0 kVA
ETI0001-2210 1.5 kVA
ETI0001-2214 3.0 kVA
ETI0001-2215 4.0 kVA
ETI0001-2221 2.2 kVA
ETI0001-2227 1.0 kVA
ETI0001-2227AA 1.0 kVA
ETI0001-2227AB 1.0 kVA
ETI0001-2227AC 1.0 kVA
ETI0001-2227AD 1.0 kVA
ETI0001-2227AG 1.0 kVA
ETI0001-2227E 1.0 kVA
ETI0001-2228 1.5 kVA
ETI0001-2228AA 1.5 kVA
ETI0001-2228AC 1.5 kVA
ETI0001-2228E 1.5 kVA
ETI0001-2229 2.0 kVA
ETI0001-2229AG 2.0 kVA
ETI0001-2229AM 2.0 kVA
ETI0001-2229E 2.0 kVA
ETI0001-2250 2.0 kVA
ETI0001-2250AB 2.0 kVA
ETI0001-2258 1.5 kVA
ETI0001-2275 2.0 kVA
ETI0015-2221 1.1 kVA
ETI0015-2222 2.0 kVA

ETI Part Number: ETI0001-1287AA
Rugged Mil Spec® 1000 VA 
Rackmount Tactical UPS

L-3 Communication / SPD Technologies Standard Product
Military Power® Isolated Mil Spec 1000 VA UPS
Rugged Rack Mount, Modular Power System

SPD Technologies P/N: 777156
NSN: 6130-01-547-8933


P/N: ETI0001-1287AA Rugged Mil Spec UPS Standard Front Panel Layout
NSN: 6130-01-547-8933


P/N: ETI0001-1287AA Rugged Mil Spec UPS Standard Rear Panel Layout

The field proven Military Power® UPS line is ideally suited for military, industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in shipboard, airborne, vehicular, field deployed or fixed locations with controlled or uncontrolled environments. The ETI0001-1287AA was specifically designed to mount in the TAC-4 racks and interface with either the TAC-4 PDU or any of numerous ETI PDUs. 

The heavy-duty chassis occupies only 5.25" (3U) of rack space while delivering up to 1000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aid in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provide easy installation and removal of the unit with full extension. Rear shock isolation/alignment bushings off load the slides when the unit is fully engaged.

The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) input voltages. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. For field deployed scenarios, the Cold Start feature allows the unit to run from its battery module before external AC is available. The input switch and the galvanic isolation transformer all provide a double pole isolated source for all installations including shipboard systems or overseas locations where phase references and grounding are not consistent. 

The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments, yet is easily adjustable to suit quieter conditions. All controls and protective devices are brought to front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. 

The rear panel provides locking connectors for the input and output power with various optional configurations available. This reverse air flow version draws air through the front and exhausts out the rear vent into the rack. A removable and washable intake air filter and high capacity stainless steel ball bearing fan provide added protection in both controlled and hostile environments. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The two status D shell connectors provide both a contact and serial interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability.

See the Power Distribution Units section for a listing of stand alone PDUs. See the N5 Series for versions of UPS with an integrated PDU and remote control.

Overall, the Military Power  line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

Technical Specifications:
P/N: ETI0001-1287AA
NSN: 6130-01-547-8933

AC OUTPUT
Output voltage: 120 VAC true sinewave standard, others optional
Output rating: UPS 1000 VA standard in 3U chassis
0.65-0.75 pf std, optional configurations to 24,000 VA
Non-linear load capacity: Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz output available as an option
Operational status Status, load and battery LEDs, w/contacts
RS-232 asynchronous serial status COM port
Adjustable level,+90 dB audible alarm w/on/off
AC INPUT
Input voltage selection: Nominal 115 VAC
Input voltage tolerance: UPS 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 70 Hz standard, optional to 440 Hz
Input power factor: Better than 99% typically
Input/output isolation: 1000 VA, >120 dB common mode, <1.0 mA leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole circuit breaker plus fuse
Guarded cold start to turn on w/o AC present
Input power connection: MS 3102A-22-2P, 3 pin, locking
INTERNAL BATTERY
Battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
Battery life: Rated for continuous service life of 5 years
DC protection: Front panel mounted fuse standard, breaker optional
Battery time: 10+ minutes @ 100% load, 25+ minutes @ 50%
Battery recharge: Recharged to nominal in <8 hours
DISTRIBUTION PANEL
Output circuits: One output standard, optional configurations
Output control: Via operation of Main Input CB1
Output receptacles: MS 3470W-14-4S, 4 pin locking, other options
MECHANICAL
Dimensions ( H x D x W ): 5.25 (3U) x 19.6 x 19.0 in (133 x 498 x 483 mm)
Rack Slide Mount Patterns: Jonathan and General Devices slide patterns, others optional
Rack rear alignment pins: (2) shock isolation/alignment pin/socket sets
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight: 75 lb. (34 kg) with folding lift handles front and rear
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: High capacity, negative pressure, forced air
Cooling air direction: Front intake, exhaust to rear, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C) with fully charged batteries
Operating temperature: -4° to 131° F ambient ( -20° to 55° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 15,000 ft (4,572 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 standard
OPTIONAL ACCESSORIES
  Autoranging International Input, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface10BaseT Ethernet SNMP/HTTP portTransport Cases

This page was last modified on: April 12, 2012
The N5 is one of the most popular configurations for new programs!

  Request Information

ETI Rugged Power UPS are the proven Standard!

Home Up Products Representation Employment News Resources Search Feedback

Send questions or comments about this web site to sales@ruggedsystems.com.
Copyright © 1991-2012 Energy Technologies, Inc. All Rights Reserved. Last modified: April 10, 2012
1st Energy™, 1st Power™, 911 Power™, AC anytime™, AC anywhere™, AC backup™, Airborne UPS™, Air Force Backup™, Air Force UPS™, Army UPS™, Backup AC™, Backup Source™, Backup The Web™, Battle Power™, Blackout Prevention™, Business Back UPS™, clean UPS™, Coast Guard Power™, Coast Guard UPS™, Controlling Power™, DC backup™, Disaster Recovery Gear™, Eco Power Source™, eDocs Port™, Energy Tech™, ETI™, Expeditionary Solar™, Extreme Power Source™, Global Power Source™, Global UPS™, Homeland Security Surveillance™, Humanitarian Power™, Hybrid Energy Storage™, Improved Power™, Industrial Backup™, Intelligent PDU™,  Intelligent UPS™, Internet Power Manager™, Lab Power™, Lab UPS™, Light UPS™, Know Power™, Marine Corps Power™, Marine UPS™, Medical Grade Power™, Military Backup™, Navy Power™, Navy UPS™, Network Power Manager™, Office UPS™, open UPS™, Personal Power Source™, Petro Chem Power™, Pipeline Power™, Portable Power Plant™, Powering The Net™, Power Protection™, Power Security™, Preventing Blackouts™, Radar Power™, Railroad Power™, Redundant Power™, Renewable Source™,  Rugged Power™, Rugged Systems™, Rugged UPS™, SCADA power™, Security Gate Power™, Shipboard Power™, Shipboard UPS™, Signal Backup™, Solar Backup™, Solar Power Source™, Soldier Power™, Tactical Computers™, Tactical Medical Office™, Tactical Office™, Tactical Solar Fly™, Tactical Trailer™, Tactical Water Plant™, Telecom Power Source™, the Warfighter™, Traffic Backup™, Traffic Signal Backup™, UPStart™, Utility Backup™, and Warfighter Power™  are trademarks of Energy Technologies, Inc.

Airborne Power®, Diplomatic Power®, Expeditionary Power®, Extreme UPS®, Hybrid Energy Technologies®, Industrial Power Source®, Military Power®,  Mil Spec®, Personal Solar®, Tactical Cables®, Tactical Cooling®, Tactical Computer Workstation®, Tactical Data Vault®, Tactical Field Office®, Tactical Fuel Cells®, Tactical Generator®, Tactical Inverter®, Tactical Micro Grid®, Tactical Power®, Tactical Power Plant®, Tactical Shelter Systems®, Tactical Solar®, Tactical Solar Shelter®, Tactical UPS®, Tactical Vehicle Power®, Tactical Wind Turbine® and Ultimate Survival Gear® are registered trademarks of Energy Technologies, Inc.

Legal Statements